FA  | EN

Interactive Fire Control Panel IFS7002 – four signal loops

Interactive Fire Control Panel IFS7002 with four signal loops is designed to operate with addressable automatic fire detectors and manual call points. It controls addressable executive devices integrated into fire alarm loops.


PRODUCT DESCRIPTION


Interactive Fire Control Panel IFS7002 with four signal loops is designed to operate with addressable automatic fire detectors and manual call points. It controls addressable executive devices integrated into fire alarm loops. The addressable executive devices can be power supplied from the fire alarm loop or from a power loop. The panel has outputs provided for integration of external executive devices.

unnamed  PC software for IFS7002  
unnamed Instruction manual for Software for PC connection of IFS7002 system    
unnamed Instruction manual – v6  
unnamed Service instructions for staff IFS7002-4
unnamed Brochure for IFS7002 – 4 signal loops

 

 

 

 

 

 

 

 

 

 

 

 

 

   

Technical data

Physical configuration:
– 4 fire alarm loops
– 1 power loop
– 2 monitored outputs
– 1 relay outputs for fire condition
– 1 programmable relay output for fire condition
– Stage I and/or stage II
– 1 relay output for fault conditions

Fire alarm zones
– Maximum number of zones: 500
– Maximum number of fire detectors in a zone: 60

Fire alarm loops
– Maximum number of fire detectors in a loop: 125
– Connecting line: two-wire shielded
– Maximum consumption of a loop: 200 mA

Power Loop
– Connecting line: two-wire
– Maximum consumption of the loop: 1А

Monitored outputs: 2 pcs
– Type: potential
– Electrical characteristics: (24±5)V/1A

Relay output for fire condition: 1 pc
– Type: potential free, switching
– Electrical characteristics: 3A/125V AC; 3A/30V DC

Programmable relay output: 1 pc
– Type: potential free, switching
– Electrical characteristics: 3A/125V AC; 3A/30V DC

Relay outputs for fault condition: 1 pc
– Type: potential free, switching
– Electrical characteristics: 3A/125V AC; 3A/30V DC

Indications of registered events
– Sound signaling: built-in sounder
– Light indication: LED
– Text messages: LCD display,320х240 points, backlit

Power supply: 220/230V; 50Hz

Mains:
Back up batteries
– Battery type: lead, gel electrolyte
– Number of batteries: 2 pcs
– Connection: serial connection
– Nominal voltage of the back up battery: 2 х 12V
– Nominal capacity C20: 18 Ah
– Charge voltage: 28,2V
Power supply to external devices
– Voltage: (24±5)V
– Maximum current value (including current of monitored outputs and power loop): 5А
Dimensions: 493x464x110mm
Weight (batteries not included): 10kg

 